Model Meaning
Type | Serial number description | Specification (type) | Scope of use |
GZD(W) 30-□/□ | Single battery pack, segmented single busbar, two dual line output charging float charging devices, no voltage reduction circuit | 10 | Power plants or large substations |
GZD (W)31-□/□ | Single battery pack, single busbar, two dual line output charging float charging devices, no voltage reduction circuit | 10 | Power plants or large substations |
GZD (W) 32-□/□ | 单Battery pack, segmented single busbar, two dual line output charging float charging devices | 20 | 12kV220kV substations and small and medium-sized power plants |
GZD (W) 33-□/□ | Single battery, dual bus, two dual line output charging float charging devices | 20 | 12kV220kV substations and small and medium-sized power plants |
GZD (W) 34-□/□ | Single battery pack, dual bus segmented, two sets of three wire output charging float charging device | 20 | 12kV220kV substations and small and medium-sized power plants |
GZD (W) 35-□/□ | Single battery, dual bus, two sets of three wire output charging float charging device | 20 | 12kV220kV substations and small and medium-sized power plants |
GZD (W) 40-□/□ | Dual battery pack, segmented single busbar, two dual line output charging float charging devices, no voltage reduction circuit | 10 | Important power plants or large substations |
GZD (W)41-□/□ | Dual battery pack, dual busbar, two dual line output charging float charging devices | 12 | 12kV220kV substations and small and medium-sized power plants |
GZD (W) 42-□/□ | Dual battery pack, dual bus segmented, two dual line output charging float charging devices | 10 | Important power plants or large substations |
GZD (W) 43-□/□ | Dual battery, single busbar, two sets of three wire output charging float charging device | 12 | 12kV220kV substations and small and medium-sized power plants |
Conditions of Use
Altitude: not exceeding 2000m.
Environmental temperature:- 5 ℃~+40 ℃.
Humidity condition: not exceeding 90% (at 20 ± 5 ℃).
Note: Special conditions can be resolved through negotiation with our company.
major function
Complete specifications: This series of products has ten models and hundreds of specifications, which can fully meet the needs of large, medium, and small sizes.
The demand for DC power supply in power plants, substations, and various industries.
Reliable operation: AC dual input automatic switching, this product is equipped with two charging float charging devices.
Mutual backup, easy system switching.
Stable operation: This product has good anti-interference performance, stable current, high voltage stabilization accuracy, and small ripple coefficient.
Long battery life: This product can strictly charge and float charge the battery according to the charging curve, avoiding overcharging or undercharging. The microcomputer controlled type has battery inspection function.
Multiple protection: This product can track and detect various working points. Combining software and hardware protection, the insulation detection device constantly monitors the condition of the busbar edge.
Sports communication: The microcomputer controlled DC power cabinet can communicate with the microcomputer, enabling centralized monitoring and unmanned operation.
Technical Parameter
Input power supply voltage: three-phase AC 380V+10%, 50Hz ± 5%
Rated output DC voltage: 24V; 48V; 110V; 220V
Rated output DC power supply: 5A, 8A, 10A, 15A, 20A, 30A, 40A, 50A, 80A, 100A, 150A, 200A, 250A, 300A, 350A, 400A
Rated capacity of battery: 10Ah, 20Ah, 38Ah, 40Ah, 50Ah, 60Ah, 65Ah, 80Ah, 100Ah, 150Ah, 200Ah, 250Ah, 300Ah, 400Ah, 500Ah, 600Ah, 800Ah, 1000Ah
Voltage regulation range (see table)
Output DC power regulation range: 0-100% of rated value
Voltage stabilization accuracy:< ±1%
Steady current accuracy:< ±1%
Ripple factor:< 1%
Whole machine noise:< 55dB
Main transformer temperature rise:< 70℃
Working mode: Continuous work
Efficiency:> 90%
Protection level: IP20~IP30
Rated output DC voltage | 24V | 48V | 110V | 220V |
Floating voltage regulation range | 21~28 | 43~57 | 99~130 | 198~260 |
Adjustment range of average charging voltage | 27~31 | 54~62 | 125~140 | 198~286 |
Main charging voltage regulation range | 21~36 | 43~70 | 99~162 | 187~310 |
Phone: 028-88808282
Fax: 028-88740872
Address: 16 Chuangye Road, Qionglai Industrial Park, Sichuan Province#