ch
产品展示

产品展示

current position: Home > Product Center > Oil Transformation Series
S22-30-1600kVA/10kV oil transformer series power transformer

S22-30-1600kVA/10kV oil transformer series power transformer

  • Category:Oil Transformation Series
  • Browse number:
  • QR code:
  • Release time:2025-01-17 17:06:13
  • Product description

Product standards

GB 1094.1       GB 1094.2          GB 1094.3          GB 1094.5

GB/T 6451      GB/T 7595          GB/T 10237       JB/T 3837


Special conditions of use

Altitude:> 1000m.


Environmental temperature:


The highest temperature is+40 ℃.


The minimum temperature is -45 ℃.


(Please provide detailed instructions when placing an order)



normal condition

Altitude: ≤ 1000m.


Environmental temperature:


The highest temperature is+40 ℃.


The highest daily average temperature is+30 ℃.


The highest annual average temperature is+20 ℃.


The minimum outdoor temperature is -25 ℃.


Supply scope: We can provide S9, 10, 11, 13 type products and meet customer requirements.



Technical Parameter

30kVA~1600kVA three-phase double winding non excited voltage regulating distribution transformer


PRODUCT MODEL

Voltage combination

Connection group label

loss(W)

no-load current

(%)

short circuit impedance I

(%)

Track gauge

(mm)

high pressure

(HV)

Tapping range of high voltage

low pressure

(LV)

Empty load

load(75℃)

S13-30/10

11


10.5


10


6.3


6

±5%


±2×2.5%

0.4

D yn11


Y yn0

85

600/630

1.8

4.0

400

S13-50/10

111

870/910

1.6

400

S13-63/10

128

1040/1090

1.5

400

S13-80/10

153

1250/1310

1.5

400

S13-100/10

170

1500/1580

1.4

550

S13-125/10

204

1800/1890

1.4

550

S13-160/10

238

2200/2310

1.3

550

S13-200/10

289

2600/2730

1.2

550

S13-250/10

340

3050/3200

1.1

550

S13-315/10

408

3650/3830

1.1

550

S13-400/10

485

4300/4520

1.0

660

S13-500/10

578

5150/5410

1.0

660

S13-630/10

689

6200

0.9

4.5

660

S13-800/10

833

7500

0.8

820

S13-1000/10

978

10300

0.8

820

S13-1250/10

1156

12000

0.7

820

S13-1600/10

1394

14500

0.6

820

Note: The values above the diagonal line are for the Yyno connection group transformer; The value below the diagonal line is for the Dyn11 connection group transformer.